Skip to main content
Clean Hydrogen Partnership

Explosion at the chlorine electrolyser of a water treatment plant

Event

Event ID
94
Quality
Description

An explosion occurred at a tank of the chlorine electrolyser of a water treatment plant
The plant products were sodium hypochlorite as a disinfectant for water treatments. The production process used was electrolysis of NaCl brines, which has hydrogen as by-product and has to be vented.
Perhaps, the cause of this event was the erroneous closure of the hydrogen vent line, forcing the hydrogen gas into the liquid holding tank where it accumulated.
During a maintenance stop, plant workers had drained the tank to within a few inches, to be able to repair a leak. They lowered then an electric pump into the tank to remove the remaining liquid. When the pump was switched on, the tank exploded.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
North America
Country
United States
Date
Component involved
chemical storage tank
Failure mode
internal explosion
Initiating cause
accidental hydrogen entrance
Root CAUSE analysis

The INITIATING cause was the ignition of the hydrogen present in the NaCl tank.

According to the investigation of the company CHEMAXX, the presence of hydrogen in the tank was probably due to the failure of the hydrogen venting system, or an error when operating it.

A component of the ROOT CAUSE was probably a shortcoming or wrong procedure (ill-designed or wrongly implemented). Upstream of this fact, the safety design was not able to guarantee failure-proof venting.

Root causes
Date entry in HIAD
28/02/2009

Facility

Application
Chemical industry
Sub-application
Chlorine production
Hydrogen supply chain stage
All components affected

hydrogen vent, NaOCl storage tank, pump, switch

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Location type
Unknown
Location
industrial area
Operational condition
Pre-event occurrences

At the moment of the explosion maintenance works were ongoing on the NaOCl tank.

Description of the facility/unit/process/substances

DESCRIPTION OF THE PROCESS
The water treatment plant used an electrolytic process to generate sodium hypochlorite (NaOCl) from a solution of sodium chloride (NaCl):
NaCl + H2O + ENERGY → NaOCl + H2

The on-site generation of sodium hypochlorite for water and wastewater disinfection has the advantage to provide the substance on demand, reducing the need for extensive on-site storage. Moreover, NaOCl is liquid, easier to handle than the gaseous chlorine.
Hydrogen as by-product mut be safety vented. Dilution blowers are normally used to this purpose. As explained by (Casson and Bess, On-Site Sodium Hypochlorite Generation, WEFTEC.06 Conference of the Water Environment Federation, 2006, Dallas, US), hydrogen dilution fans are not always used. Depending on the system location. Some systems are designed without fans because they are located away from ignition sources. Other systems use open-top tanks, and this allow hydrogen to separate and disperse. On-site generation systems typically have closed tanks; therefore, fans are required for normal dilution.

Emergency & Consequences

Number of fatalities
1
Number of injured persons
0
Investigation comments

The main issues investigated by Chemaxx (company that carried out investigation) focused on the mechanisms and rates by which hydrogen gas is generated and subsequently accumulated in the holding tank. The need for active venting, warning signs and incidents of a similar nature were also reviewed.

Lesson Learnt

Lesson Learnt

The vent system of the on-site NaOCl electrolyser was a critical component of the safety design. Hydrogen had to be discharged to the atmosphere in a safe way, avoiding cumulation in the NaOCl tanks or in the venting system.
Although little is known on the reason why the system failed to vent hydrogen, it out of doubts that it was not well equipped with the required safeguards able to avoid or mitigate vent obstruction, wrong operation or hydrogen cumulation. Detection of hydrogen and out-of-spec operative conditions detection should have been in place to trigger an alarm and possibly automatic corrective actions.

Corrective Measures

The company that carried out investigation (Chemaxx) identified the need to ensure active venting hydrogen. They required also warning signs and the implementation of an alarm system able to detect failure of the venting system.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Probable IGNITION SOURCE
Explosion type
Detonation

References

Sources categories
Investigation report
Reference & weblink

originally a CHEMAXX investigation, not available anymore.

This event is also in H2TOOLS,
https://h2tools.org/lessons/hydrogen-explosion-water-treatment-facility
(accessed December 2025)

For an overview of the NaOCl process, incuding safety handling:
Casson and Bess,
On-Site Sodium Hypochlorite Generation,
WEFTEC.06 Conference of the Water Environment Federation - Oct. 21-25, 2006, Dallas, US