Skip to main content
Clean Hydrogen Partnership

Fire in a refinery plant

Event

Event ID
93
Quality
Description

The event occurred in an alkylation reactor. Due to the rupture of a pipe (probably due to material failure), a power failure took place and the plant was automatically put in hot-stand-by mode. This implied the cut out of fuel feed and energy supply. The plant was gradually cooled down.
After about half an hour, for reasons not yet clarified, a fire started at the outlet of the alkylation reactor.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
Germany
Date
Component involved
pipe (generic)
Failure mode
rupture & ignition
Initiating cause
material degradation (generic)
Root CAUSE analysis

The INITIATING cause was the rupture of the pipe feeding into the reactor, probably due to material failure.
How this relates to the development of a fire later is unknown. The investigation report is not available.

Root causes
Unknown
Date entry in HIAD
28/02/2009

Facility

Application
Petrochemical industry
Sub-application
alkylation process
Hydrogen supply chain stage
All components affected

alkylation reactor, feeding pipe

Location type
Open
Location
industrial area
Operational condition
Pre-event occurrences

The accident occurred during normal operation of the plant. However, fire started after that a shutdown caused by the failure of a pipe.

Description of the facility/unit/process/substances

DESCRIPTION OF THE PROCESS
An alkylation unit is one of the many conversion steps taking place in petroleum refineries. It converts isobutane and low-molecular-weight alkenes (primarily a mixture of propene and butene) into alkylate, a high octane gasoline component. The process occurs in the presence of an acid as catalyst. The feeds contains as well non-condensable gases such as ethane and hydrogen.
(from Wikipedia, https://en.wikipedia.org/wiki/Alkylation_unit)

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Currency
Euro
Property loss (onsite)
2.500.000
Post-event summary

The total establishment and the potential directly involved inventories of hydrogen, methane, benzene and toluene has been estimated in about 10,000 Kg. This figure refers to the whole amount involved in the accident. No data are available about their single amounts.
No people injured. The cost of the material damages estimated between 2 to 5 millions of Deutsch Marks.

Emergency action

Emergencies actions were necessary only inside the plant.

The emergency depressurization of the plant was activated. In order to minimize the amount of flammable substances involved, the isolation of various sections of the plant was carried out. Nitrogen purging of the system was carried out. The adjacent installations were protected by applying cooling water.

The fire was extinguished by the intervention of operators, the plant fire brigade and the local fire brigade. The fire fighting water was collected in a basin and disposed for treatment in the biological waste-water treatment plant of the establishment. Ambient air monitoring inside the establishment revealed no presence of hazardous substances in the environment.

In-depth data

Release type
gas mixture
Involved substances (% vol)
H2,
CH4,
C6H6,
toluene
Released amount (kg)
1000
Probable IGNITION SOURCE
Flame type

References

Sources categories
eMARS
Reference & weblink

Event description in the European database eMARS
https://emars.jrc.ec.europa.eu/en/emars/accident/view/f484c24a-cb04-e46…
(accessed September 2020)

Event description in the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/801/