Fire in a diesel distillation unit

Event

Event ID
85
Quality
Description

A jet flame occurred in a diesel distillation unit.
It was caused by the release and ignition of hydrogen from the low-pressure (60 bar) section of a the unit. It occurred during maintenance works aiming at replacing the temporary seals with definitive ones, after which the discharge valve would have been re-opened and the compressor re-started.

The unit was depressurised and the emergency status was called.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
France
Date
Component involved
valve (gasket)
Failure mode
erroneous release & ignition
Initiating cause
malfunctioning (electrical/electronic component)
Root CAUSE analysis

The INITIATING cause was the fact that the discharge valve was not completely closed even though the panel control indicated that it was entirely closed.
The ROOT CAUSE could be attributed to a wrong design, which did not considered the possibility of a wrong signal on a critical component for safety.

Root causes
Date entry in HIAD
28/02/2009

Facility

Application
Petrochemical industry
Sub-application
diesel distillation unit
Hydrogen supply chain stage
All components affected

Gasoil distillation unit , seals

Location type
Unknown
Location
industrial area
Operational condition
Pre-event occurrences

Maintenance works were ongoing on the compressor on recycled gas circuit. Temporary seals had to be replaced by definitive seals.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Official legal action

The independent inspection required a root cause analysis and a detailed examination of the tightness of the automatic valve.

Emergency action

Rescue units were on site but they did not make an attempt to extinguish the fire to avoid the formation of a hydrogen cloud. The affected unit was depressurised. After 50 minute the leak was closed and the fire extinguished. Shortly afterward the alarm was terminated.

Lesson Learnt

Corrective Measures

The plant operator modified the system controlling the opening of the affected valve during the maintenance works.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Probable IGNITION SOURCE

References

Sources categories
ARIA
Reference & weblink

Event 33030 in the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/33030/
(accessed October 2020)