Event
- Event ID
- 51
- Quality
- Description
An explosion followed by a fire occurred at a refinery, due to the rupture of a hydrogen line inside a hydrogen heater.
Since the refinery control room noticed something wrong with the equipment’s readings, an employee was sent to check on the hydrogen heater. Sometime its arrival on location, the explosion occurred.
The reason for the release remained unknown.- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Macro-region
- North America
- Country
- United States
- Date
- Component involved
- heat exchanger (pipe)
- Failure mode
- internal explosion
- Initiating cause
- unknown
- Root causes
- Unknown
- Date entry in HIAD
- 28/02/2009
Facility
- Application
- Petrochemical industry
- Sub-application
- Unspecified refinery process
- Hydrogen supply chain stage
- All components affected
unknown
- Location type
- Unknown
- Location
- industrial area
- Operational condition
- UNKNOWN
- Description of the facility/unit/process/substances
DESCRIPTION OF THE PROCESSES
The ' hydrogen heater' affectted by the incident was probably the fired heater used to pre-heat the feedstock to a refinery process such as a hydron-cracker or hydro-desuplphurisation unit (see for example HIAD_656).
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 1
- Post-event summary
One injured worker sustained second and third degree burns to his back and face.
The hydrogen heater suffered heavy structural damage
No off-site impact.- Emergency action
Large water cannons, permanently mounted throughout the sprawling facility, were used to cool the hydrogen heater. Officials also injected nitrogen into the line to purge the remaining hydrogen and allowed it to burn off.
Lesson Learnt
- Lesson Learnt
Rupture of hydrogen or process gases tubes in pre-heaters /heat-exchangers / fired heaters is a recurrent event up to recent times. This is not surprising, considering the high temperatures and pressures involved. The most common causes are materials degradations due to manufacturing defects and operative stresses. Ruptures tend to happen during operative transients, which may cause over-heating due to reduction of flows. When the releases occur also in presence of naked flames, as in fired heaters, which use conventional fuels burners, ignition and explosion in the confined of the heater box is ensured. Nevertheless, due to sturdy heater constructions, it rarely happens that damage extends to the outside environment.
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Probable IGNITION SOURCE
- Explosion type
References
- Sources categories
- News
- Reference & weblink
KSLA news od 03 March 2004
https://www.ksla.com/story/1684394/explosion-at-shreveport-refinery-inj…
(accessed Decemebr 2023)Online news
http://www.ci.shreveport.la.us/dept/fire/2004/040303.CalumetExplosion.h…
(link unavailable)HIAD 1.0 reporting template (Original source unavailable).