Event
- Event ID
- 11
- Quality
- Description
The incident occurred at the hydrocracker unit, which was being shut down for maintenance and the reactor was in a hydrogen purge cycle. A hydrogen gas line failed at a weld. The line was at 3000 psi (approx. 200 bar), resulting in a high-pressure hydrogen fire.
(1) The fire impinged on the calcium silicate insulation of the skirt of the hydrocracker reactor.
(2) The skirt failed causing the fall of the reactor.
(3) The falling reactor damaged air coolers and other process equipment, greatly increasing the size of the loss.
The initial hydrogen leak is believed to have resulted from the failure of an elbow to reducer weld in the hydrogen preheat exchanger by-pass line.- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- fire
- Macro-region
- North America
- Country
- United States
- Date
- Component involved
- pipe (weld)
- Failure mode
- rupture & ignition
- Initiating cause
- material degradation (generic)
- Root CAUSE analysis
The INITIATING cause was the failure of a pipe welding.
This caused a domino effect with an escalation of the risks and the damages.
This suggests a incorrect design risk assessment as ROOT CAUSE. In the course of the evolution of the events, also shortcoming of the management of he emergency procedures became evident.- Root causes
- Date entry in HIAD
- 28/02/2009
Facility
- Application
- Petrochemical industry
- Sub-application
- Hydrocracking process
- Hydrogen supply chain stage
- All components affected
2-inch pipeline, protective steel skirt of a reactor, reactor ,nearby equipment
- Process pressure range [MPa]
- medium to high pressure (10 to 50 MPa)
- Location type
- Open
- Location
- industrial area
- Operational condition
- Pre-event occurrences
At the time of the event, the hydrocracker unit was in the process of being shut down for maintenance. The reactor was in a hydrogen purge cycle.
Emergency & Consequences
- Number of fatalities
- 7
- Number of injured persons
- 8
- Currency
- US $
- Property loss (onsite)
- 90.000.000
- Post-event summary
source MARSH reports a total financial damage of $90 Million (currently $200 Million).
Only ICHEME report fatalities.
Lesson Learnt
- Corrective Measures
(general, related to the management of emergency, not technical, related to the improvement of the reduction of the technical risk)
(1) Flame Resistant Clothing: a flame resistant clothing policy at all the refineries belonging to the own. Flame resistant clothing will be provided to and worn by all employees working in designated mandatory areas of the refineries.
Exception: employees merely passing through a mandatory area, not performing a task that could result in contact with a flash fire, or performing a task in a shutdown processing area that could not result in contact with a flash fire).
Mandatory areas: Hydro-processing, Cracking, Distillation and Reforming, Cat/Wax, Blending and Shipping and Utility Divisions.
(2) Turn Out Gear: to have available and require the use of turnout gear, by any operators who are requested by the incident commander to perform an operating function in the hot zone during a fire. (Hot zone is an area inside the perimeter established by the incident commander, where the risk of burn injuries to exposed skin could occur by flame contact or radiant heat).
(3) To reinforce owner’s policy as to operators' duties and responsibilities during the post-incipient stage of a fire. This includes outlining the general scope of operators' duties during an emergency; the use of flame resistant clothing and turnout gear during such emergencies; and that non-fire brigade operations personnel are not to enter the hot zone during a fire unless and until the incident commander so requests and turn out gear is provided and donned.
(4) To communicate this policy to all affected employees, in the form of a Refinery Instruction.
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Probable IGNITION SOURCE
- Flame type
References
- Sources categories
- ICHEME
- Reference & weblink
Event nr 4537 of the UK database ICHEME in PDF format
https://www.icheme.org/knowledge/safety-centre/resources/accident-data/
(accessed October 2020)MARSH report, 100 largest losses in the hydrocarbon industry, 27th edition 2022
https://www.marsh.com/cz/en/industries/energy-and-power/insights/100-la…
(accessed January 2024)OHSA ssttmement agreement
https://www.osha.gov/enforcement/cwsa/chevron-usa-inc-and-the-chevron-r…
(accesed January 2024)Wikipedia page dedicated to the plant, mentions the incident:
https://en.wikipedia.org/wiki/Chevron_Richmond_Refinery#cite_note-13
(accessed December 2023)